Valvole riduttrici di pressione
ACV Ratio Reducing Valve
Fixed-ratio PRV for network pressure management.
Descrizione del prodotto
The ACV ratio reducing valve maintains a fixed ratio between upstream and downstream pressure: as inlet pressure varies, the outlet pressure varies proportionally. This is particularly useful on systems where demand patterns cause large upstream pressure fluctuations, as it avoids the very low outlet pressures that a fixed-set-point PRV would deliver at low inlet pressures. Fully hydraulic, no external power required.
Specifiche tecniche
Gamma di diametriDN50–DN400
PressionePN16
MaterialeDuctile iron body, rubber-lined diaphragm, stainless pilot
CollegamentoFlanged to EN 1092-2 PN16
Approvazioni e certificazioni
WRASWater Regulations Advisory Scheme: UK approval for use in drinking water systemsISO 9001International quality management system certification
Norme
EN 1074-5
Applicazioni tipiche
- Trunk main pressure management
- Variable inlet pressure systems
- District metered areas
- Pressure zone management

Richiedi un preventivo
Inviateci il diametro nominale, la classe di pressione e la quantità e risponderemo con i prezzi e la documentazione tecnica completa, tipicamente entro un giorno lavorativo.
Richiedi un preventivo oppure scrivete a info@afcvalves.euIn sintesi
- Diametri
- DN50–DN400
- Pressione
- PN16
- Collegamento
- Flanged to EN 1092-2 PN16